C200HW-BI101-V1 Omron, C200HW-BI101-V1 Datasheet - Page 89

no-image

C200HW-BI101-V1

Manufacturer Part Number
C200HW-BI101-V1
Description
BACKPLANE, 10 SLOT, I/O EXP
Manufacturer
Omron
Datasheet

Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Wiring
Output Surge Current
3-2-3 Electrical Noise
I/O Signal Lines
74
When connecting a transistor or triac Output Unit to an output device having a
high surge current (such as an incandescent lamp), care must be taken to avoid
damage to the Output Unit. The transistor and triac Output Units are capable of
withstanding a surge current of ten times the rated current. If the surge current
for a particular device exceeds this amount, use the circuit shown below to pro-
tect the Output Unit.
Another way of protecting the Output Unit lets the load draw a small current
(about one third the rated current) while the output is OFF, significantly reducing
the surge current. This circuit (shown below) not only reduces the surge current,
but also reduces the voltage across the load at the same time.
Whenever possible, place I/O signal lines and power lines in separate ducts or
tubes. If placing them together cannot be avoided, use shielded cable to mini-
mize the effects, and connect the shielded end to the GR terminal.
Suspended duct
PC
PC
COM
COM
OUT
OUT
In-floor duct
R
R
L
L
1 = I/O cables
2 = Power cables
Section 3-2
Conduits
+
+