Specifications
C200H-OD21A Transistor Output Unit (16 Points, Sourcing)
(Load Circuit Protection Provided)
Circuit Configuration
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM
146
Terminal Connections
output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to
Max. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Load Short-circuit Protection
Power for External Supply
Weight
Alarm Output (See note 1.)
Reset Input
Load Short-circuit Protection
Dimensions
5 to 24 VDC
Output
indicator
L
L
L
L
L
L
COM
2 kΩ
NC
NC
11
1
3
5
7
9
A0
A1
A2
A3
A4
A5
A6
A7
A8
24 VDC
0.1 mA max.
0.8 V max.
0.1 ms max.
0.3 ms max.
1 (16 points/common)
160 mA 5 VDC max.
Detection current: 1.2 A min (1.6 A typical)
35 mA 24 VDC
400 g max.
No. of outputs: 1 (2 kΩ internal resistor)
Connectable Units: Only the following DC Input
Units can be connected:
C200H-ID001, ID211, ID212, IM211 (DC), IM212
(DC), ID215, ID501, MD115, MD215, MD501
Used when alarm output turns ON. Value will
depend on the external power supply. (See note 2.)
Detection current: 1.2 A min.
(1.6 A typical)
B-shape
0 V
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
to
10
NC
NC
NC
NC
0
2
4
6
8
+10%
L
L
L
L
L
L
/
–15%
+10%
, 1.0 A (4 A/Unit)
/
–15%
min.
Appendix B