Clearing the Alarm
When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm indicator will go
out, the alarm output will turn OFF, and the output will be reset.
Programming Example
If there is a short-circuit in an output, we want the program to turn that output OFF. Assume that the Unit is mounted
at word 000. A program to turn OFF output bits 00 and 01 is shown below.
Since alarm output bit 08 covers both output bits 00 and 01, both these outputs are forced OFF as soon as output
bit 08 turns ON (bits A and B can be any other bits required in the program).
Transistor Output Unit C200H-OD216
144
Circuit Configuration
Internal
Circuit
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
A
B
00008
00008
Output indicator
Alarm indicator
Reset button (use a screwdriver
or other similar object to press it).
OUT
OUT
COM
0.3 A 5 to 24 VDC
10 mA 5 VDC
0.1 mA max.
1.5 V max.
1.5 ms max.
2 ms max.
1 (8 points/common) positive common (source
type)
10 mA 5 VDC max. 75 mA 26 VDC (8 points ON
simultaneously.)
None
N/A
250 g max.
A-shape
L
L
00000
00001
5 to 24 VDC
Appendix B