Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Voltage Fluctuation
Inspections
5-3
Handling Precautions
92
1
2
3
4
5
No.
Main power
supply
Ambient
environment
e
I/O power
supply
Installation
Consumable
parts
Inspections
o
Item
e
Check the voltage fluctuations at
the power supply terminals.
Measure the temperature inside
the control panel.
Measure the humidity inside the
control panel.
Check for dirt and dust.
Check the voltage fluctuations at
the I/O terminals.
Check the mounting of all Units.
Check all cable connections.
Check all external wiring screws.
Check all external wiring cables.
Contact output Relays:
G6B-1174P-FD-US
24 VDC
Battery: C200H-BAT09
Daily and periodic inspections are required to keep PCs working in top condition.
PC are constructed out of semiconductor components, which although have an
extremely long life time, can deteriorate under improper environmental condi-
tions. Periodic inspections are thus required to ensure that the required condi-
tions are being kept.
Inspection is recommended at least once every six months to a year, but more
frequent inspections will be necessary in adverse environments.
Take immediate steps to correct the situation if any of the conditions in the follow-
ing table are not met.
• Always turn off the power supply before replacing a Unit.
• After replacing a faulty Unit, check the new Unit to make sure that the same
• When returning a Unit for repairs, provide as many details about the problem
• To clean bad contacts, use a clean cotton cloth soaked in industrial alcohol and
100 to 120 VAC
200 to 240 VAC
24 VDC
5. Replace the cover of the battery compartment.
6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF
problem does not appear again.
as possible in writing and attach it to the Unit before delivering it to your
OMRON representative. (See inside back cover for regional offices.)
be sure to remove any threads from the cloth before mounting the Unit.
and then ON again to clear the error message on the Programming Con-
sole.
Contents
Power supply voltage
The voltage must be within the
allowable voltage fluctuation (see
following table)
Temperature must be 0 to 55 _C.
Humidity must be 35% to 85%.
There must be no collection of dirt
and dust.
Voltages must be within
specifications for each Unit.
The Units must be firmly mounted.
The cables must be firmly connected.
The screws must be firmly tightened.
The cables must not be damaged in
any way.
Electrical life
Mechanical life: 50 million operations
Expected life: 5 yrs at 25 _C
Resistive loads: 300,000 operations
Inductive loads: 100,000 operations
Criteria
85 to 132 VAC
170 to 264 VAC
19.2 to 28.8 VDC
Allowable voltage fluctuation
Voltage tester
Thermometer
Humidity meter
Visual
Voltage tester
Phillips
screwdriver
Phillips
screwdriver
Visual
Visual
---
---
Section 5-3