Inspection and Maintenance
5-2-2 Replacing Relays
Replacement Relay
88
1, 2, 3...
Note
Note The relays on the C200H-OC222N, C200H-OC224V, and C200H-OC226 can-
The following Output Units provide relay sockets that allow the Relays to be
replaced if they should go bad. Use the Relay listed in the table.
Use the following procedure to replace a Relay.
not be replaced.
C200H-OC221
C200H-OC222
C200H-OC223
C200H-OC224
C200H-OC225
C200H-OC222V
C200H-OC224V
C200H-OC226
4. Using a Phillips screwdriver, remove the screw from the top of the Unit.
5. Using a flat-blade screwdriver, detach the case from the Unit.
6. Pull out the printed circuit board.
7. Insert a new fuse. A spare fuse is provided inside the rear of the case when
8. Reassemble in reverse order of assembly.
1. Use UL or CSA approved fuses if the UL or CSA standards must be satis-
2. Fuses in High-density I/O Units cannot be replaced by the user. Refer to
1. Turn OFF the power to the PC.
2. Detach the terminal block by unlocking the lock levers at the top and bottom
the Unit is delivered.
fied. For further details, consult the fuse manufacturer.
your OMRON dealer for service.
of the terminal block.
Output Unit
G6B-1174P-FD-US
24 VDC
24 VDC
G6R-1, 24 VDC
Relay
(4)
Rear of the case
Spare fuse
(5)
Section 5-2