C200HW-BI101-V1 Omron, C200HW-BI101-V1 Datasheet - Page 223

no-image

C200HW-BI101-V1

Manufacturer Part Number
C200HW-BI101-V1
Description
BACKPLANE, 10 SLOT, I/O EXP
Manufacturer
Omron
Datasheet

Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
Wiring
Terminal Names and Allocations
The use of the terminals depends on the model of the B7A Interface Unit. “m” indicates the first word allocated to
the Unit according to the I/O number setting and can be calculated as follows:
208
C200H-B7A22
C200H-B7A21
C200H-B7A12
B0
B1
B2
B3
B4
B5
B6
B7
B8
A0 to A7
B9
A8
B0
B1
B2, B3
B4
B5
B6 to B8
A0 to A7
B9
A8
B0
B1
B2, B3
B4
B5
B6 to B8
A0 to A7
B9
A8
Terminal
Terminal
Terminal
SIG OUT1
– OUT1
SIG OUT2
– OUT2
SIG IN1
– IN1
SIG IN2
– IN2
NC
+V
–V
SIG OUT1
– OUT1
NC
SIG IN1
– IN1
NC
+V
–V
SIG IN1
– IN1
NC
SIG IN2
– IN2
NC
+V
–V
Name
Name
Name
m = 030 + (2 x I/O number)
Connect to SIG terminal on Output B7A Link Terminal.
Connect to – power supply terminal on Output B7A Link
Terminal.
Connect to SIG terminal on Output B7A Link Terminal.
Connect to – power supply terminal on Output B7A Link
Terminal.
Connect to SIG terminal on Input B7A Link Terminal.
Connect to – power supply terminal on Input B7A Link
Terminal.
Connect to SIG terminal on Input B7A Link Terminal.
Connect to – power supply terminal on Input B7A Link
Terminal.
Not used.
Connect to + terminal on external power supply.
Connect to – terminal on external power supply.
Connect to SIG terminal on Output B7A Link Terminal.
Connect to – power supply terminal on Output B7A Link
Terminal.
Not used.
Connect to SIG terminal on Input B7A Link Terminal.
Connect to – power supply terminal on Input B7A Link
Terminal.
Not used.
Connect to + terminal on external power supply.
Connect to – terminal on external power supply.
Connect to SIG terminal on Input B7A Link Terminal.
Connect to – power supply terminal on Input B7A Link
Terminal.
Not used.
Connect to SIG terminal on Input B7A Link Terminal.
Connect to – power supply terminal on Input B7A Link
Terminal.
Not used.
Connect to + terminal on external power supply.
Connect to – terminal on external power supply.
Function
Function
Function
Appendix B
m
m + 1
m + 2
m + 3
NA
m
NA
m + 1
NA
m
NA
m + 1
NA
Word
Word
Word

Related parts for C200HW-BI101-V1