C200HW-BI101-V1 Omron, C200HW-BI101-V1 Datasheet - Page 162

no-image

C200HW-BI101-V1

Manufacturer Part Number
C200HW-BI101-V1
Description
BACKPLANE, 10 SLOT, I/O EXP
Manufacturer
Omron
Datasheet

Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
Terminal Connections
Note When the ALARM output turns ON, remove the cause of the high current and then shut off the external
Triac Output Unit C200H-OA122-E
the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit
and the indicator at the same time. Unless the external I/O power supply is connected and turned ON, the
indicator will not light even if the output contact turns ON.
power supply for approx. 1 second. After confirming that the cause has been removed, turn ON the power
supply again to reset the output. As shown in the diagram, it is recommended that a relay or switch that turns
ON or OFF only the external power supply be connected right before the B9 (+V). Check that this relay or
switch has a contact capacity higher than the external power supply current consumption (35 mA + load
current minimum).
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
24 VDC
0 V
+24 VDC
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
N/A
300 g max.
E-shape
Appendix B
147