C200HW-BI101-V1 Omron, C200HW-BI101-V1 Datasheet - Page 102

no-image

C200HW-BI101-V1

Manufacturer Part Number
C200HW-BI101-V1
Description
BACKPLANE, 10 SLOT, I/O EXP
Manufacturer
Omron
Datasheet

Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Inspection and Maintenance
5-2
5-2-1 Replacing Output Unit Fuses
Inspection and Maintenance
1, 2, 3...
The following Output Units each contain one fuse. Replace the fuse if the fuse
indicator lights. The OD211, OD212, OA222, and OA224 Output Units do not
have fuse indicators. Replace the fuses on these Units if outputs are not pro-
duced.
The OD411, OD213, OA221 and OA223 Output Units also provide an external
output bit that can be used to check the condition of the fuse. If bit 08 of the word
allocated to the Unit is ON, the fuse is burnt out.
To replace a fuse, follow the steps below. Use only UL/CSA certified replace-
ment fuses.
C200H-OD411
C200H-OD211
C200H-OD212
C200H-OD213
C200H-OA221
C200H-OA222V
C200H-OA223
C200H-OA224
1. Turn OFF the power to the PC.
2. Detach the terminal block by unlocking the lock levers at the top and bottom
3. While pushing down the lock lever on the Backplane with a screwdriver as
of the terminal block.
shown below, remove the Output Unit.
Unit
Yes
No
No
Yes
Yes
No
Yes
No
Fuse indicator
125 V, 5 A
125 V, 8 A
250 V, 5 A
250 V, 3 A
250 V, 5 A
250 V, 3.15 A
Lock lever
(20 mm long x 5.2 mm dia.)
,
,
Capacity
Section 5-2
87