Recommended Cables and Transmission Distance
The following cables are recommended to connect the B7A Interface Unit to B7A Link Terminals. The wiring meth-
od and transmission distance depend on the transmission delay and on whether or not a common power supply is
being used for the B7A Link Terminal and the Interface Unit.
Standard Transmission Delays (19.2 ms): Cap-tire Cable
High-speed Transmission Delays (3 ms): Shielded Cable
Terminal Construction
Wiring Method
Standard Transmission Delays (19.2 ms)
Common
Separate
Common
Separate
Power supply
Power supply
Common Power Supply
B7A Interface Unit
VCTF, 0.75 mm
VCTF ,0.75 mm
Shielded cable, 0.75 mm
Shielded cable, 0.75 mm
12 to 24 VDC
C200H-B7A02
B0
B1
B2, B3
B4
B5
B6 to B8
A0 to A7
B9
A8
Terminal
Use hook-type crimp connectors with a line thickness of 0.25 to 1.65 mm
construction of the terminals is shown in the illustration.
2
2
x 3 conductors
x 2 conductors
Cable
Cable
SIG OUT1
– OUT1
NC
SIG OUT2
– OUT2
NC
+V
–V
Transmission cable: VCTF 0.75 mm
Name
Transmission distance: 100 m max.
2
2
x 3 conductors
x 2 conductors
Connect to SIG terminal on Output B7A Link Terminal.
Connect to – power supply terminal on Output B7A Link
Terminal.
Not used.
Connect to SIG terminal on Output B7A Link Terminal.
Connect to – power supply terminal on Output B7A Link
Terminal.
Not used.
Connect to + terminal on external power supply.
Connect to – terminal on external power supply.
100 m max.
500 m max.
50 m max.
100 m max.
Transmission distance
Transmission distance
2
or higher
Function
B7A Link Terminal
B7A Link Terminal
Appendix B
m
NA
m + 1
NA
Word
2
. The
209