Error Codes and Error Flags
Note 1. Operation will be switched to the standby CPU Unit in Duplex CPU Systems.
A20011: First Cycle Flag
546
Auxiliary Area Allocations
System-defined fatal errors
User-defined fatal errors
User-defined non-fatal errors
System-defined non-fatal errors 009A
2. C101 to C2FF will be stored for FALS numbers 001 to 511.
3. 4101 to 42FF will be stored for FAL numbers 001 to 511.
4. The contents of the error flags for a duplicate number error are as follows: Bits 0 to 7: Unit number
5. Only the contents of A295 is stored as the error flag contents for program errors.
6. 0000 hex will be stored as the error flag contents.
7. The rightmost digit of the error code (0 to F) for duplex communications error corresponds to CPU
8. These error occur only for Duplex CPU Systems.
9. These error occur only for Single CPU Systems or Process-control CPU Units.
Classification
(binary), 00 to 5F hex for Special I/O Units, 00 to 0F hex for CPU Bus Units,
Bits 8 to 14: All zeros, Bit 15: Unit type, 0 for CPU Bus Units and 1 for Special I/O Units.
Bus Unit unit numbers 0 to F.
80F1
80F0
809F
82F0
80C0 to 80C7,
80CF
80E9
80E1
80E0
80EA
C101 to C2FF FALS instruction executed (See notes 1
4101 to 42FF
009B
00E7
02F0
0200 to 020F
0300 to 035F
00F7
0400 to 040F
0500 to 055F
0011
0010
0003
0600 to 060F
Error code
Execution
started.
Memory error (See note 1.)
Program error (See note 1.)
Cycle time overrun error (See note 1.)
Fatal Inner Board error (See notes 1 and
9.)
I/O bus error
Duplicate number error
Too many I/O error
I/O setting error
Duplicate Expansion Rack number error A40900 to 40907
and 2.)
FAL instruction executed (See note 3.)
Basic I/O Unit error
PLC Setup setting error
I/O verification error
Non-fatal Inner Board error (See note 9.) A424
CPU Bus Unit error
Special I/O Unit error
Battery error
CPU Bus Unit setup error
Special I/O Unit setup error
Duplex verification error (See note 8.)
Duplex bus error (See note 8.)
Duplex power supply error
Duplex communications error (See note
7.)
One cycle
Meaning
Time
A403
A294 to 299 (See note 5.)
---
A424
A404
A410, A411 to 416
(See note 4.)
A407
---
---
---
A408
A406
---
A417
A418 to 423 (See note 6.)
---
A427
A428 to 433 (See note 6.)
A31600, A317, A804
A31601
A31602, A319
A31603, A321, A434 to A437
Error flags