244
FINS Commands
CPU Bus Unit Initialization
Data Exchange with CPU Bus Units
Serial Communications
Unit
Transferred when power is turned
on or the Unit is restarted.
CPU Bus Unit
Some models transfer data in both directions, from the DM Area to the Unit
and from the Unit to the DM Area. See the Unit’s Operation Manual for details
on data transfers.
These 100 words are generally used to hold initial settings for the CPU Bus
Unit. When the contents of this area are changed from the program to reflect a
change in the system, the Restart Bits (A50100 to A50115) for affected Units
must be turned ON to restart the Units.
The CMND(490) instruction can be added to the ladder program to issue a
FINS command to the CPU Bus Unit.
FINS commands can be transmitted to CPU Bus Units in other PLCs in the
network, not just the local PLC.
CPU Bus Units are initialized when the PLC’s power is turned on or the Unit’s
Restart Bit is turned ON. The Unit’s CPU Bus Unit Initialization Flag (A30200
to A30215) will be ON while the Unit is initializing.
Cyclic I/O refreshing will not be performed for a CPU Bus Unit while its Initial-
ization Flag is ON.
Command transmission
CPU Unit
CPU Bus Unit
CPU Bus Unit
FINS command transmission
Transferred each cycle
and when necessary.
Serial Communications Unit
CPU Unit
CPU Unit
CPU Unit
DM Area for CPU Bus Units
100 words/Unit
The FINS command is transmitted
when CMND(490) has been
executed in the program.
The FINS command is transmitted
when CMND(490) has been
executed in the program.
Section 7-6