CS1D-II102D Omron, CS1D-II102D Datasheet - Page 449

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Error Processing
10-2-12 Battery Error Check
10-2-13 Environmental Conditions Check
414
Battery error occurred.
Battery-free operation
required?
No
Environmental conditions check
Yes
Is the ambient humidity
temperature below
temperature above
environment okay?
between 10% and
Is noise being
Is the installation
Is the ambient
Is the ambient
controlled?
vibration?
Is there
55 C?
90%?
0 C?
End
Yes
Yes
Yes
Yes
Yes
(See note.)
No
No
No
No
No
Note: Check for corrosive gases,
Install the PLC where there
is less vibration.
Set the PLC Setup so that battery
errors are not detected. (DM Area
contents may be unstable when this
setting is used.)
Refer to the CS/CJ Programming
Manual for details.
The Battery is missing or the voltage
has dropped. Replace the Battery.
Consider using a fan or
cooler.
Consider using a heater.
Consider using an air
conditioner.
Install surge protectors or
other noise-reducing
equipment at noise sources.
Check the structure of the
panel and the installation
site.
flammable gases, dust, dirt,
salts, metal dust, direct light,
water, oils, and chemicals.
Section 10-2