CS1D-II102D Omron, CS1D-II102D Datasheet - Page 312

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Auxiliary Area
Non-fatal Duplex Errors
Non-fatal Duplex Error Flag
Duplex Verification Error Flag
(See note.)
Duplex Bus Error Flag (See
note.)
Duplex Power Supply Unit
Error Flag
Duplex Communications Error
Flag
Duplex Verification Error Flag
Other CPU Unit Duplex Verifi-
cation Error Flag
CPU Unit Model Verification
Error Flag
CPU Unit Version Verification
Error Flag
Inner Board Model Verification
Error Flag (Process-control
CPU Units only)
Parameter Area Verification
Error Flag
No Active CPU Unit Error Flag A31714
User Program Verification
Error Flag
Ethernet Duplex Setting Flag
Unit Removal without a Pro-
gramming Device Function
Setting Flag
Duplex Verifications Errors (Duplex CPU Systems Only)
Name
Name
Note Duplex CPU Systems only.
A40214
A31600
A31601
A31602
A31603
A31600
A31706
A31707
A31708
A31710
A31713
A31715
A80400
A80401
Address
Address
ON: One of the following errors occurred: Duplex
verification error, duplex bus error, duplex power
supply unit error, or duplex communications error
(See note.)
ON: An inconsistency exists between the program
or memory of the active and standby CPU Units in
Duplex Mode. (Refer to A317, A804 for details.)
ON: An error occurred on the sync transfer bus in
the duplex system.
ON: An error occurred in the Power Supply Unit or
power supply system on a duplex CPU Rack,
Expansion Rack, or Long-distance Expansion
Rack.
ON: One of the duplex Communications Units has
failed. (Refer to A434 to A437 for details.)
ON: An inconsistency exists between the program or mem-
ory of the active and standby CPU Units in Duplex Mode.
(Refer to A317, A804 for details.)
ON: A duplex error occurred in the other CPU Unit when
entering Duplex Mode.
ON: The CPU Units were not the same model when entering
Duplex Mode.
ON: The unit version of the standby CPU Unit is earlier than
the unit version of the active CPU Unit and the active CPU
Unit uses function not supported by the standby CPU Unit.
ON: The duplex Inner Boards in the two Process-control
CPU Units were not the same model when entering Duplex
Mode.
ON: The parameter area in the two CPU Units in duplex
mode do not have the same contents.
ON: There is no active CPU Unit for CPU Unit set for
standby operation when power was turned ON in duplex
mode. This occurs when one of the following is detected:
The active CPU Unit is not mounted, the CPU Unit switch is
set to NO USE, or pin 7 on the DIP switch is set for simple
backup operation.
ON: The user program in the two CPU Units in duplex mode
do not have the same contents.
ON: The unit version of the standby CPU Unit is earlier than
the unit version of the active CPU Unit and the active CPU
Unit uses a PLC Setup setting (Ethernet Duplex Setting) that
is not supported by the standby CPU Unit.
ON: The unit version of the standby CPU Unit is earlier than
the unit version of the active CPU Unit and the active CPU
Unit uses a PLC Setup setting (Unit Removal without a Pro-
gramming Device Function Setting) that is not supported by
the standby CPU Unit.
Description
Description
Duplex Verifications
Errors
Duplex Power Supply
Errors
Duplex Communica-
tions Errors
Duplex Verifications
Errors
---
Duplex Power Supply
Errors
Duplex Communica-
tions Errors
Reference
Section 8-11
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Access
277