CS1D-II102D Omron, CS1D-II102D Datasheet - Page 490

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
11-5 Replacing Power Supply Unit
11-6 Replacement of Expansion Units
Replacing Power Supply Unit
POWER
!WARNING
PA207R
L2/N
L1
100-120
CLOSE
200-240
OPEN
AC100V-120V/
AC2100-240V/
INPUT
RUN
OUTPUT
AC240V
DC24V
2A RESISTIVE
1,2,3...
Power
supply
AC power supply
Voltage selector:
Screws (3.5 mm head with
self-raising pressure plate)
Remove the short bar before applying 200 to 240 V AC.
Closed for 110 V AC
Open for 220 V AC
Use the following procedure to replace a Power Supply Unit when ever it is
necessary to replace it, e.g., when an error is detected in the Power Supply
Unit or for periodic maintenance.
1. Turn OFF the power supply to the Unit to be replaced and remove the wir-
Do not touch any live terminals. You will receive an electric shock.
2. Remove the Power Supply Unit.
3. Mount a new Power Supply Unit, making sure it is the same model of CS1D
4. Connect the wiring that was removed to the new Power Supply Unit.
5. Turn ON the power supply to the Unit and confirm that the POWER indica-
6. Clear the error from the CPU Unit and check A31602 to confirm that there
With a Duplex CPU Dual I/O Expansion System, a CS1D I/O Control Unit or
CS1D I/O Interface Unit can be replaced when an error occurs in the Unit or
during periodic maintenance. Use the following procedure to replace an
Expansion Unit.
RUN output
ON when the CPU Unit is in RUN or MONITOR mode.
OFF when the CPU Unit is in PROGRAM mode or when a fatal error has occurred.
ing. If the RUN output is being used in the external sequence circuits, ei-
ther keep the RUN output shorted when removing the wires or prepare the
sequence circuits so that they will be no adverse affects when the RUN
output wires are removed.
Power Supply Unit.
tor lights.
is no error in the Power Supply. If there is no error, then this completes the
replacement procedure.
1:1 isolating
transformer
AC power source
100 to 200 V AC
200 to 240 V AC
Section 11-5
455

Related parts for CS1D-II102D