CS1D-II102D Omron, CS1D-II102D Datasheet - Page 186

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Interlock Circuits
5-2
5-2-1
Ambient Conditions
Installation
Installation
Installation and Wiring Precautions
Note Do not latch the RUN output and use it in a circuit to stop a controlled object.
Chattering of the relay contacts used in the output may cause incorrect opera-
tion.
When the PLC controls an operation such as the clockwise and counterclock-
wise operation of a motor, provide an external interlock such as the one
shown below to prevent both the forward and reverse outputs from turning ON
at the same time.
This circuit prevents outputs MC1 and MC2 from both being ON at the same
time even if both CIO 000501 and CIO 000502 are both ON, so the motor is
protected even if the PLC is programmed improperly or malfunctions.
Be sure to consider the following factors when installing and wiring the PLC to
improve the reliability of the system and make the most of the PLC’s functions.
Do not install the PLC in any of the following locations.
Output Unit
• Locations subject to ambient temperatures lower than 0 C or higher than
MCB1
55 C.
MCB2
000501
000502
Transformer
or noise filter
PLC RUN
output
Twisted-pair wires
Interlock circuit
CR1
MC2
MC1
CR1
Controlled system
Power supply
MC1
MC2
CS1D PLC
in Duplex Mode
DC voltage
regulator
Surge suppressor
Motor clockwise
Motor counterclockwise
+
DC
input/output
Section 5-2
151