CS1D-II102D Omron, CS1D-II102D Datasheet - Page 219

no-image

CS1D-II102D

Manufacturer Part Number
CS1D-II102D
Description
CS1D Dual IO Interface Unit
Manufacturer
Omron
Datasheet

Specifications of CS1D-II102D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Wiring Methods
Output Wiring Precautions
Output Short-circuit
Protection
Transistor Output
Residual Voltage
Output Leakage Current
184
4. Precautions on Sensor Surge Current
If a load connected to the output terminals is short-circuited, output compo-
nents and the and printed circuit boards may be damaged. To guard against
this, incorporate a fuse in the external circuit. Use a fuse with a capacity of
about twice the rated output.
A TTL circuit cannot be connected directly to a transistor output because of
the transistor’s residual voltage. It is necessary to connect a pull-up resistor
and a CMOS IC between the two.
If a Triac Output Unit is used to drive a low-current load, the leakage current
may prevent the output device from turning OFF. To prevent this, connect a
bleeder resistor in parallel with the load as shown in the following diagram.
An incorrect input may occur if a sensor is turned ON after the PLC has
started up to the point where inputs are possible. Determine the time re-
quired for sensor operation to stabilize after the sensor is turned ON and
take appropriate measures, such as inserting into the program a timer de-
lay after turning ON the sensor.
Example
In this example, the sensor’s power supply voltage is used as the input to
CIO 000000 and a 100-ms timer delay (the time required for an OMRON
Proximity Sensor to stabilize) is created in the program. After the Comple-
tion Flag for the timer turns ON, the sensor input on CIO 000001 will cause
output bit CIO 000100 to turn ON.
V
V
V
I
I
R
TIM0000 000001
ON
OFF
000000
SYSMAC
CC
ON
OFF
IN
: PLC ON current
: PLC input impedance
: Power voltage
: PLC ON voltage
: PLC OFF current
: PLC OFF voltage
Two-wire sensor
TIM
OUT
COM
000100
#0001
0000
L
V
Bleeder resistor
R
V
I
I
R: Bleeder resistance
V
OUT
leak
R
CC
: Sensor output residual current
: Sensor leakage current
: Sensor control current (load current)
R
R
IN
Load power
supply
DC Input Unit
Section 5-4

Related parts for CS1D-II102D