Handling Precautions
9-6-3
C200HX/HG/HE and CQM1H-series Controller Link Units
Using the Controller Link
Support Software
Not Using the Controller
Link Support software
Replacing the Unit
!Caution When a C200HX/HG/HE or CQM1H-series Controller Link Unit has been
1,2,3...
1,2,3...
Note When manually set data links are used, the Controller Link Support Software
replaced or a CPU Unit has been replaced for a CS/CJ-series, CVM1, or CV-
series Controller Link Unit, do not connect that node to the Network before
carrying out the above procedures. In particular, a node with a small address
will become the polling node and communicate the initial network parameter
status to other nodes, so there is the chance that network parameters in the
entire Network will be damaged.
1. From the Maintenance Menu on the Controller Link Support Software, se-
2. Turn off all nodes in the Controller Link Network.
3. Detach the communications cables and the Bus Connection Unit attached
4. Mount the new Controller Link Unit in the PLC and connect the communi-
5. Set the node address, baud rate, operating level (front DIP switch,
6. Turn on only those PLCs for which Units were replaced.
7. From the Maintenance Menu on the Controller Link Support Software, se-
8. Cycle the power supply to the PLC where the Unit was replaced.
9. Turn on all other nodes in the Controller Link Network.
10. Using the Controller Link Support Software, read the network parameters
11. If the data links are not activated automatically, activate the data links from
12. Check that the data links are operating normally by using the “Data Link
is essential. When the Controller Link Unit being replaced does not have
active manually set data links or it has active automatically set data links, the
replacement process can be carried out without the Controller Link Support
Software. In this case, however, a Programming Device is necessary.
1. Turn off all nodes in the Controller Link Network.
2. Detach the communications cables and the Bus Connection Unit attached
3. Mount the new Controller Link Unit in the PLC and connect the communi-
lect “Unit Back-up” and then “Unit –> Computer.” The data will be saved as
a file in the Unit’s EEPROM.
Data link tables and network parameters are saved in this way.
to the Controller Link Unit to be replaced and remove the Unit.
cations cables and the Bus Connection Unit. (Refer to SECTION 3)
C200HX/HG/HE only) and the terminating resistance for the new Unit to
the same settings as the previous Unit. (Refer to SECTION 4.)
lect “Unit Back-up” and then “Computer –> Unit” and the data saved in step
1. will be loaded to the Unit’s EEPROM.
and make sure the Network is operating normally.
the data link startup node.
Status Monitor” on the Controller Link Support Software.
to the Controller Link Unit to be replaced and remove the Unit.
cations cables and the Bus Connection Unit. (Refer to SECTION 3.)
Section 9-6
325