4-5-2
4-5-3
Node Addresses
Baud Rates
Note
Note Always turn OFF the PLC’s power before setting the baud rate.
Set the node address of each Unit in the Network using the rotary switch on
the front of the Unit. The node address is used to identify each node in the
Network.
The node address can be set to any value between 01 and 32.
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
1. Always turn OFF the PLC’s power before setting the node address.
2. Do not set the same node address twice within the same Network. An error
3. The send sequence for the data link areas is determined according to the
4. Assign node addresses consecutively beginning from 01 whenever possi-
Set the following pins for the baud rate setting (DIP switch).
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
Setting method
Setting range
Node
OFF
ON
OFF
ON
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light and either communications will stop,
or the INS indicator will not light and you will be unable to participate in the
Network.
sequence of node addresses for automatically set data links.
ble to minimize Network construction time.
Note The factory default setting is shown in bold.
Pin 1
Item
Switch
OFF
OFF
ON
ON
Pin 2
BAUD RATE
2-digit decimal
01 to 32 (default is 01)
All nodes in the Network
NODE NO.
2 Mbps
1 Mbps
500 Kbps
Do not set.
X10
X10
Baud rate
1
0
ON
SW1
Specifications
500 m
800 m
1 km
transmission distance
Maximum
Section 4-5
103