4-1-4
Baud Rate (Pins 1 and 2)
90
CS-series Controller Link Units
Baud Rates
Note
4. When CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-
5. To construct a network that uses a node address higher than 32, it is nec-
6. Only node addresses 1 through 32 can be used on networks for which 62
7. The Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
8. The send sequence for the data link areas is determined according to the
9. Assign node addresses consecutively beginning from 01 whenever possi-
Set the following pins for the baud rate settings (DIP switch).
1. Always turn OFF the PLC’s power before setting the baud rate.
2. Keep pins 3 and 4 set to OFF.
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
OFF
ON
OFF
ON
ther communications will stop, or the INS indicator will not light and you will
be unable to participate in the Network.
CLK23 Units are used with other models in the same network, set the node
addresses of all nodes between 1 and 32. In a network containing pre-ver-
sion-1 models, it is not possible to construct a network that uses a node
address higher than 32.
Turn ON the Wired Network 62 Node Enable Bit (bit 11 of D30000 + 100 ×
Unit No.) in the DM Parameter Area software switch of all CS1W-CLK21-
V1, CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23 Units to restrict
the network to 32 nodes maximum. If a different value is specified, the net-
work will be incorrectly configured.
essary for all nodes to be CS1W-CLK21-V1, CS1W-CLK23, CJ1W-
CLK21-V1, or CJ1W-CLK23 Units.
In addition, the Wired Network 62 Node Enable Bit in the DM Parameter
Area software switch of all nodes must be turned ON to enable using 62
nodes maximum. If a different value is specified, the network will not be
correctly configured.
nodes have not been enabled.
ware switches of CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, and
CJ1W-CLK23 Units is read when the Unit is restarted.
sequence of node addresses for automatically set data links.
ble to minimize Network construction time.
Note The factory default setting is shown in bold.
Pin 1
Note: The factory default settings are shown above.
Pins
OFF
OFF
ON
ON
Pin 2
Pins 3, 4: Not used (must be OFF)
Pins 1, 2: Baud rate
2 Mbps
1 Mbps
500 Kbps
Do not set.
Baud rate
transmission distance
500 m
800 m
1 km
Maximum
Section 4-1