Introduction
(↑)SEND(192)
S
D
C
C+1
C+2
S: Source node beginning send word
D: Destination node beginning receive word
C: Source node first control data word
C
15
15
15
Destination node N
01 to 20 (Hex): 1 to 32 (or 01 to 3E (Hex): 1 to 62)
The same data can be broadcast to all nodes
on the network by setting the destination node address to
FF (Hex).
The range of node addresses will vary for networks
other than Controller Link Networks.
0
Note
"n" number of send words
0001 to 03DE (Hex): 1 to 990 words
11
11
0
8 7
8 7
Destination network address
00 (Hex):
01 to 7F (Hex): 1 to 127
SEND transmits “n” words beginning with S (the beginning word for data
transmission at the source node) to “n” words beginning with D (the beginning
word for data reception at the destination node, N.)
1. When using CVM1 and CV-series PLCs manufactured prior to April 1996,
2. With the message service, there is no guarantee that a message to a des-
Destination unit address
00 (Hex):
01 to 0F (Hex): Computer (user program)
10 to 1F (Hex): Unit nos. 0 to 15
FE (Hex):
the local network address cannot be set to “00.” Set a number other than
“00” as the local network address in the routing tables, and then specify
that number.
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
using the message service, it is advisable to prevent this situation from oc-
curring by performing resend processing at the node where instructions
are issued. With the SEND, RECV, and CMND instructions, resend pro-
cessing is performed automatically once the number of retries has been
set, so be sure to specify a number other than “0” for the number of retries.
0
0
0
Local network
PLC's CPU Unit
(02 to 0F (Hex) are used
when using Controller Link
Support Boards for PCI Bus
only.)
Unit connected to network
C+3
C+4
15
S
0: Response required
1: Response not required
0
15
10 8 7
Source node
Communication port No.
0 to 7
Response monitor time
0000 (Hex): 2 s
0001 to FFFF (Hex): 0.1 to 6,553.5 s
(Unit: 0.1 s)
If the baud rate is slow, then setting a small
value may generate an error. The standard is
approximately 4 seconds at 1 Mbps or 8
seconds at 500 Kbps.
0
0
"n" number
of send
words
n
3
Number of retries
0
0 to F (Hex): 0 to 15 retries
Destination node N
D
15
Section 6-1
0
n