CV500BC101 Omron, CV500BC101 Datasheet - Page 220

no-image

CV500BC101

Manufacturer Part Number
CV500BC101
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC101

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Using the Message Service
C200HX/HG/HE and
CQM1H-series PLC
Response Codes
CS/CJ-series, CVM1, and
CV-series Response
Codes
The results of executing SEND and RECV instructions are reflected as shown
in the following table.
The results of executing SEND, RECV, and CMND instructions are reflected
as one word (two bytes) of data. Instruction response codes are the same as
FINS command response codes. Response code bits 08 to 15 correspond to
the first byte of the response code, and response code bits 00 to 07 corre-
spond to the second byte of the response code. For details, refer to 6-7
Response Codes.
00 (Hex)
01 (Hex)
02 (Hex)
03 (Hex)
04 (Hex)
05 (Hex)
06 (Hex)
07 (Hex)
08 (Hex)
09 (Hex)
10 (Hex)
11 (Hex)
12 (Hex)
Code
Normal end
Parameter error
Transmission impossible
Destination node error
Destination node busy
error
Response timeout
Response error
Communications control-
ler error
Setting error
CPU Unit error
Routing error
Relay error
Source node busy error
Contents
Data transfer was completed successfully.
SEND/RECV instruction operands are not
within specified ranges.
The source node is not in the network or
the Unit was reset during execution of the
instruction.
The destination node is not in the network.
The destination node is busy and cannot
receive the command.
A response was not received within the
time limit.
The response received from the destina-
tion node was incorrect.
An error occurred in the communications
controller.
The destination node address was set
incorrectly.
A CPU Unit error occurred in the PLC of
the destination node.
Command could not be sent because of
incorrect routing.
Command did not reach the destination
node because of an error at the relay sta-
tion.
The source node is busy and cannot send
the command.
Meaning
Section 6-3
195

Related parts for CV500BC101