198
Using the Message Service
(Continued from the previous page)
Execution
condition
000001
120003
120002
120002
120002
120002
(See note 1.)
(See note 1.)
A20207
A20207
A21907
120003
120000
A21907
Network Instruction Error Flag
Note
1. With CS/CJ-series PLCs, the Network Instruction Enabled Flag in A20200
2. When using the sample program, make sure that the bits and words used
to A20207 corresponding to communications ports will be OFF even when
PMCR (PROTOCOL MACRO) is being executed.
in the sample program are not the same as those in the user program or
by Special I/O Units.
@MOV(21)
@MOV(21)
@MOV(21)
@MOV(21)
@MOV(21)
@RECV(98)
DIFU(13) 120003
@XFER(70)
S
KEEP(11)
120002
D00005
D00006
D00007
D00008
D00009
D00005
D00040
121001
#0010
#0003
#2000
#0705
#0000
#0016
A100
2000
2000
R
Control Data Preparation
The reception program will run when CIO 00001
turns ON, provided that the Network Instruction En-
abled Flag is ON and the SEND instruction has not
been executed.
CIO 120002 remains ON while the RECV instruction
is being executed, and it turns OFF when instruction
execution has been completed.
Transfers the 16 words beginning at A100 of net
work address 3, node address 32, and Unit address
0 (PLC) to 2000.
Creates reset input.
Turns ON to indicate reception error.
Transmitted data (16 words from 2000) moved into
words beginning at D00040 for storage.
D00005
D00006
D00007
D00008
D00009
Word
Content
0 0
0 0
2 0
0 7
0 0
10
0 3
0 0
0 5
0 0
16 send words
Destination network
address= 3
Destination node
address = 32
Destination Unit
address = 0
Response required
Port No. 7 used
No. of resends = 5
Response monitoring
time = Default
Meaning
Section 6-3