Handling Precautions
9-5-1
9-5-2
Tools and Equipment Need for Inspection
Inspection Items
9-6
Handling Precautions
Cleaning
Inspection
!Caution Do not use volatile solvents such as benzine or paint thinner, or chemical
Conduct the following periodic cleaning to keep the Controller Link Unit in
optimum condition.
cloths for cleaning. They will damage the quality of the coating on the Unit.
Controller Link Units must be inspected on a regular basis to ensure correct
operation. Inspections should be conducted once every 6 to 12 months. If the
Unit is subject to extremes in temperature or humidity, inspections should be
conducted on a more regular basis.
The following tools and equipment will be needed to perform inspection and
adjustments.
Inspect the follow items to see if they deviate from the prescribed standards. If
any items do deviate from the standard either adjust so they are within the
operating range or adjust the Unit accordingly.
The Controller Link Unit is a Network device. If the Unit is damaged, it will
effect the entire Network, so always ensure repairs are undertaken immedi-
ately. We recommend that you have a spare Controller Link Unit on hand so
that repairs may be conducted quickly.
Ambient condi-
tions
Installation
• Wipe the Unit with a dry, soft cloth daily.
• For stains that cannot be removed with a dry cloth, dip the cloth in
• If glue, vinyl, or tape is left on the Unit for long periods of time, it will stain.
• Assorted flat-blade and Phillips screwdrivers
• Circuit tester or digital voltmeter
• Industrial-grade alcohol and clean cotton cloth
• Synchroscope
• Pen-chart recording oscilloscope
• Thermometer, hygrometer
medium strength alcohol (2%), wring the cloth tightly, and then wipe down
the Unit.
Remove these items during cleaning.
Item
Temperature: 0° to 55°C
Humidity: 10% to 90% (no conden-
sation or freezing)
Dust-free
Units securely attached?
Communications cable connectors
tight?
Communications cabling used for
external wiring intact (no breaks)?
Description
Thermometer
Hygrometer
Sight
Flat-blade screwdriver and
sight
Inspection instrument
Section 9-6
321