CV500BC051 Omron, CV500BC051 Datasheet - Page 78

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Component Names and Functions
3-1-4
Wired Unit Indicators
CVM1 and CV-series Controller Link Unit
X10
SW1
UNIT
NO.
X10
NODE
NO.
X10
CLK21
BAUD RATE
BIT2 BIT1
OFF
OFF
ON
BD H
BD L
SHLD
1
1
1
RUN
ERC
INS
SD
ON
0
0
OFF
ON
OFF
TER SW
1
0
1
2
3
4
RATE
2MBP
1MBP
500KBP
TER
ERH
M/A
LNK
RD
BAUD
RATE
RSV
RSV
X10
X10
0
0
RUN
(operating)
TER
(terminating
resistance)
ERC (communica-
tions error)
ERH
(PLC error)
INS
(network
participation)
M/A
(data link mode)
LNK
(data link)
Name
Indicators
LED indicators that display the Unit and network status.
Unit number switches
Two rotary switches. The unit number is set in 2-digit decimal
for the Network to which the PLC is connected.
Node address switches
Two rotary switches. The node address of the Unit on the
Controller Link Network is set in 2-digit decimal.
Baud rate switch
A four-pin DIP switch. The following setting is made.
Pins 1, 2: Baud rate
Pins 3, 4: Not used (always OFF)
Terminating resistance switch
A slide switch. Use this switch to set the terminating resistance to ON for
nodes at both ends of the Controller Link Network.
Terminal block for the communications cable
Terminals to connect to the Controller Link Network communications
cable (twisted-pair cable).
Green
Yellow
Red
Red
Yellow
Yellow
Yellow
Color
(Refer to p. 53 and 285)
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Flashing
Not lit
Status
(Refer to p. 101)
(Refer to p. 100)
Unit operating normally.
Unit error.
Terminating resistance switch ON.
Terminating resistance switch OFF.
Communications error, node address
setting error (same address set twice), or
hardware error.
Normal operation
PLC error, PLC interface error, EEPROM
error, unit number error, or I/O table not
set
No error.
Unit is participating (inserted) in the net-
work.
Unit is not participating (inserted) in the
network.
Manual
(see note)
Automatic
Data links participating.
Error in data link table.
Not in a data link or data link inactive.
(Refer to p. 100)
(Refer to p. 101)
Meaning
Note:
M/A is always not lit
when data links are not
active in the network.
(Refer to p. 68)
Section 3-1
53