CV500BC051 Omron, CV500BC051 Datasheet - Page 181

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
5-3-1
CS/CJ-series Start Bit
C200HX/HG/HE Start Bit
156
Starting and Stopping Data Links
Word N
AR 07
Using a Programming Device or the User Program
15 14 13 12 11 10 9
15 14 13 12 11 10 9
N: DM 30000 + 100 × (unit number)
Note The data in the AR and DM Areas is retained when power is turned off. There-
Set the software switch (AR or DM Start Bit) in the PLC to ON using a Pro-
gramming Device or from the user program.
The data links will start when the Start Bit changes from OFF to ON or is
already ON when power is turned on. The data links will stop when the Start
Bit changes from ON to OFF.
fore, by setting in the AR and DM Areas can be made in advance to start data
links as soon as power is turned on.
It is recommended to set the Start Bit to ON in multiple nodes that are partici-
pating in the data link so that the data links will start even if the startup node is
down. The same data link settings must be set in these nodes for automati-
cally set data links.
Programming Device
8
8
7
7
6
6
5
5
4
CX-Net
(in CX-Programmer)
4
+
3
3
2
2
1
1
0
0
Startup node
Data link Start Bit for level 0 (AR 0700)
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
Data link Start Bit of level 1 (AR 0704)
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
CS/CJ-series PLCs
Turn ON the Start Bit in DM 30000 + 100 × N.
(N: unit number)
C200HX/HG/HE PLCs
Turn ON the Start Bit in AR 07
CVM1 and CV-series PLCs
Turn ON the Start Bit in DM 2000 + 100 × N.
(N: unit number)
CQM1H-series PLCs
Turn ON the Start Bit in AR 07.
Data link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned on
Stop: Changed from ON to OFF
Controller Link
User program
Section 5-3

Related parts for CV500BC051