CQM1H-series PLCs
122
Setting Data Links
Area 2 Data link
PLC model
Nodes
Setting item
Setting item
Note a) The total number of words in data link send and receive areas
start word
Number of
words
Offset
b) The following values must be satisfied for each node for the data
c) Refer to the Controller Link Support Boards Operation Manual
d) If CX-Net detects an error during the data link table check, trou-
must not exceed 8,000 per node.
link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.
(Data link start word – 1) + Total number of send/receive
words in area
(W307) for information on the Controller Link Support Board.
bleshoot the error referring to 9-4 Troubleshooting Error Mes-
sages in CX-Net Data Link Table Check .
CIO Area: CIO 0000 to CIO 2555
LR Area:
DM Area: DM 0000 to DM 8191 (CV500/CVM1-CPU01-EV@)
EM Area: Banks 00 to 07, EM 0000 to EM 32765
The same area cannot be set for both area 1 and area 2. Set dif-
ferent areas.
*: When a word between LR 000 and LR 199 is specified, the
Remote nodes:
Local node:
The total number of words in area 1 and area 2 in each node
must not exceed 1,000.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Remote nodes:
Local node:
This setting is not required if an offset is not used.
Set the model of the PLC’s CPU Unit.
1 to 32
Set the address of the refresh nodes.
It cannot be set to a parameter exceeding the “maximum node
address” of the network parameters.
data link area will be allocated between CIO 1000 and
CIO 1199.
2555 (CIO Area)
199 (LR Area)
8191 (DM Area for CV500/CVM1-CPU01-EV@)
24575 (DM Area for other CPU Units)
32765 (EM Area)
LR 000 to LR 199 (*)
DM 0000 to DM 24575 (Other CPU Units)
(EM must be installed)
0 to the number of source words
Set the number of words to be received.
0 to 1,000
Set the number of words to be transmitted.
0 to one less than number of source words
Set the offset for the data to be received.
Cannot be set.
Setting range
Setting range
Section 5-2