CV500BC051 Omron, CV500BC051 Datasheet - Page 170

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Setting Data Links
Note
1. Node 1 becomes the master node. Node 1 must be registered as a partic-
2. Only one area can be specified when using the chain type of 1:N alloca-
3. The startup node (the node that sets the above DM parameter and starts
4. The total number of words in data link send and receive areas must not ex-
Area start word
Area
Number of master com-
mon send words
No. of receive and send
words per node
First word to store data
link status
Nodes to participate in
the data links
ipating node.
tion.
the data link) must be set as a participating node of the data link. If not, the
data links will not start.
ceed 20,000 per node when using Controller Link Units with unit Ver. 1.2
or later, or 12,000 words per node if using pre-Ver. 1.2 Controller Link
Units. The total number of words in data link send and receive areas of a
master node must satisfy the following values. Since the number of master
node words is greatest when 1:N allocation is used, the value can be esti-
mated from the number of master node words.
Item
Set the word address in BCD.
IR or CIO Area: 0 to 6143
LR Area: LR 000 to LR 199 (1000 to 1199) (*)
DM Area: DM 0 to 32767
EM Area: Banks 0 to 12 EM 0 to 32767
*: When a word between LR 000 and LR 199 is speci-
Set the area type of area 1 as a hexadecimal number.
IR Area: 80 Hex
LR Area: 86 Hex
DM Area: 82 Hex
EM Area Banks 0 to 7: 90 to 97 Hex
Set the number of words in BCD between 0 and 1,000.
The number of common send words per master node
added to the number of delivery send words per node
must not exceed 1,000.
Set to 0 if common data is not to be sent from a master
node to a slave node.
Set the number of words in BCD between 0 and 1,000.
The number of common send words per master node
added to the number of delivery send words per node
must not exceed 1,000.
Set to 0 if delivery data is not to be sent.
Set in BCD the first word used for storing data link status.
When automatic setup is used, status can be stored in
the IR or CIO Area only. The number of words used to
store status depends on the data link status storage for-
mat specification as below.
0 (*)
1 to 6128 (32 nodes max., 8-bit format: 16 words used)
*: When 0 is set, the status is saved in IR 1500 + unit
Set to ON (1) the bits corresponding to the nodes partici-
pating in the data links.
The data link will not start unless the startup node itself is
set as a participating node.
fied, the data link area will be allocated between
words 1000 and 1199 in the IR or CIO Area.
number x 25 (+ 7 to + 22).
Banks 8 to 12: A8 to AC Hex
Setting range
Section 5-2
145