CV500BC051 Omron, CV500BC051 Datasheet - Page 323

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Operating Level Status: SR 252
298
Status Area and Troubleshooting
Operating
level 0
SR 239
SR 240
SR 241
Operating
level 1
SR 243
SR 244
SR 245
Node 2
Node 4
Node 6
Note Data link status is valid only when the local node is participating in the data
link. Confirm that the local node’s data links are active in the operating level
status in SR 252 before referencing the data link status.
Node 1
Node 3
Node 5
Operating level 1
Operating level 0
1: Local node data link participating
SEND/RECV Enable Flag
0: Disabled (operating)
1: Enabled (not operating)
SEND/RECV Error Flag
0: Normal completion
1: Error
1: Local node data link participating
SEND/RECV Enable Flag
0: Disabled (operating)
1: Enabled (not operating)
SEND/RECV Error Flag
0: Normal completion
1: Error
Remaining receive area
0: Not remaining
1: Remaining
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Offset error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Error: Offset exceeds
number of send words.
Remaining: Receive area
is larger than send area.
Data is received and
remaining words are
cleared.
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.
Section 9-2