CV500BC051 Omron, CV500BC051 Datasheet - Page 339

no-image

CV500BC051

Manufacturer Part Number
CV500BC051
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC051

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
314
Error Log
0109
Hex
010A
Hex
010B
Hex
010C
Hex
010D
Hex
010E
Hex
010F
Hex
0110
Hex
0111
Hex
0112
Hex
0113
Hex
0114
Hex
0115
Hex
0116
Hex
Error
code
Transmission failed; destination
busy
Transmission failed; communica-
tions controller error
Transmission failed; PLC error
Transmission failed; unit number
incorrect
Transmission failed; destination
address incorrect
Transmission failed; routing
tables not registered
Transmission failed; routing table
error
Transmission failed; too many
relay points
Transmission failed; command
packet too long
Transmission failed; header
error.
Transmission failed; I/O setting
error
Transmission failed; CPU bus
error
Transmission failed; redundant I/
O allocations
Transmission failed; CPU Bus
Unit error
Contents
Command block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
Response block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
1st byte
Source node address
Source Network address
OFF
Destination node
address
Destination Network
address
ON
Detail code
2nd byte
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
Conduct an echo-
back test and if the
effects of noise are
considerable, recon-
sider the operating
environment. Restart
the Controller Link
Unit. If the error
occurs again,
replace the Unit.
Refer to the PLC
operating manual. If
the error occurs
again, replace the
PLC.
Check unit number
settings to be sure
they are within range
and unique.
Check routing tables. No
Check routing tables No
Check routing tables. No
Check routing tables
and system configu-
ration. Use a CS/CJ-
series CPU Unit with
unit version 2.0 or
later and CX-Pro-
grammer Ver. 4.0 or
higher to send com-
mands across three
or more network lev-
els.
Be sure to use the
FINS command
format.
Be sure to use the
correct FINS
command format.
Check I/O table
accuracy.
Check Unit and cable
connections and
clear error.
Check unit numbers
for redundancy within
the same PLC.
Check Unit and cable
connections and
clear error.
Correction
No
Yes
No
No
No
No
No
No
No
No
No
Written to
EEPROM
Section 9-3
All
All
All
CV, CS/CJ
All
All
All
All
All
All
CV, CS/CJ
CV, CS/CJ
CV, CS/CJ
CV, CS/CJ
Applicable
PLC