Data Link Procedure
28
Basic Procedures
1,2,3...
2. Set the node address on the front rotary switches.
3. Set the baud rate and operating level on the front DIP switch.
4. Set the terminating resistance on the sliding switch.
5. Connect power to all nodes.
6. Connect the Programming Device to the PLC.
7. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
8. Register routing tables as required.
CVM1, CV-series, and CS/CJ-series PLCs
1. Perform mounting and wiring.
2. Set the Unit number on the front rotary switches.
3. Set the node address on the front rotary switches.
4. Set the baud rate and operating level on the front DIP switch.
5. Set the terminating resistance on the front slide switch.
6. Connect power to all nodes.
7. Connect the Programming Device to the PLC.
8. Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
9. Set the Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
10. Register routing tables.
Set the data link mode in the data link parameters in the DM area of the star-
tup node to either automatic or manual data link creation using the Program-
ming Device.
series PLCs and not necessary for CJ-series PLCs unless user-created
I/O tables have been specified).
series PLCs and not necessary for CJ-series PLCs unless user-created I/
O tables have been specified).
ware switches. (See note b.)
Note a) Setting 62 nodes is possible only with the CS1W-CLK21-V1,
• Connect the communications cables.
• 01 to 32
• 2 M, 1 M, or 500 Kbps
• Operating level 0 or operating level 1 (C200HX/HG/HE PLCs only)
• ON or OFF (Only the end nodes are set to ON.)
• Mount to the PLC.
• Connect the communications cables.
• 00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)
• 01 to 32 (01 to 62) (See note a.)
• 2 M, 1 M, or 500 Kbps (wired systems only)
• ON or OFF (Only the terminal node is set to ON.)
• ON (62 nodes max.) or OFF (32 nodes max.)
b) This setting is valid only with the CS1W-CLK21-V1, CS1W-
CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23. The Wired
Network 62 Node Enable Bit in the DM Parameter Area software
switches must be set.
CLK23, CS1W-CLK21-V1, and CS1W-CLK23. Reset the power to
the PLC after setting.
Section 1-4