CS1W-CN625 Omron, CS1W-CN625 Datasheet - Page 211

no-image

CS1W-CN625

Manufacturer Part Number
CS1W-CN625
Description
CBL,PROG
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN625

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
5-4
5-4-4
5-4-4
5-20
Diagnosing Disconnections
Displaying Disconnection Counters
Disconnection Counter Display
Disconnection Counters
Disconnection Counters
Disconnection counters, which measure disconnections at each node, can be
displayed by diagnosing disconnections.
Select Diagnose – Display disconnection counter from the Main Menu.
• The disconnection counters that measure disconnections at each node are
• The following counter items are displayed.
displayed.
Time of beginning
disconnection data recording
Number of node/network
separations
Number of network
disconnections
Number of local node
disconnections
Maximum number of
consecutive disconnect cycles
Number of frame drop-outs
(SL1, SL2)
Number of frame brakes
detected (SL1, SL2)
Number of CRC errors
detected (SL1, SL2)
Item
Displays the time that recording disconnection information was
started. This will be the time the power supply was turned ON to
the node, the time the Unit at the node was restarted, or the
time the disconnection counters were cleared.
Displays the number of times the local node was separated from
the network.
Displays the number of disconnections detected on the network.
Displays the number of disconnections detected for the local
node.
Displays the number of communications cycles over which a
disconnection continued. Use this information to determine if a
disconnection was momentary or continuous.
Displays the number of times a data frame received at another
communications port was not received at all at the local
communications port.
Dropouts are counted when the communications line is
completely disconnected.
Displays the number of times only a carrier was detected at the
local communications port for a data frame received at another
communications port.
Brakes are counted when the optical cable is damaged, when
end surface processing is faulty, for contact faults, or whenever
else transmissions are unstable.
Displays the number of CRC errors and Manchester errors.
These errors are counted when the optical cable is damaged,
when end surface processing is faulty, for contact faults, or
whenever else transmissions are unstable.
Description