Specifications of CS1W-CN625

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3-1 Routing Table Overview
3-1-2 Network Conditions That Require Routing Tables
3-1-2
3-4
Note
Network Conditions That Require Routing Tables
Mounting Two or More Communications Units (See Note) to a Single CPU Unit
Communicating with a PLC in Another Network
Setting Routing Tables in Two or More Nodes in the Same Network
The following, however, is an exception. In this case, a local network table does not
need to be registered even if there is more than one Network Communications Unit.
If a local network table is not registered, network access will be possible to only the
network of the Communications Unit with the smallest unit number when a direct serial
connection is made to a target PLC.
Routing tables must be set for the following network conditions.
Note: Network Communications Units include Controller Link Units, Ethernet Units,
Routing table required.
Routing tables are not required when just one Communications Unit is installed in
each PLC and those Communications Units are connected in a single network.
Routing table not required.
Routing tables are required when transferring FINS messages between networks or
using the CX-Programmer's remote programming/monitoring functions between
networks.
CS/CJ-series DeviceNet Units, SYSMAC LINK Units, and SYSMAC NET Link Units.