Creating the FINS Local Routing Tables Offline
Start the Routing Table Component. (Start the PLC routing tables.)
Right-click the Communications Unit or Port in the Online Connection Information Window select Start Routing Table from the
popup menu, or select Tools - Start Routing Table from the CX-Integrator's menu bar.
Start the Routing Table Component. (Start the PLC routing tables.)
Select Tools – Start Routing Table from the CX-Integrator's menu bar.
Select the type of routing table. (Select FINS local routing tables.)
Select FINS Local from the Select Network Dialog Box.
Set the gateway counter. (CS/CJ-series CPU Units must be unit version 3.0 or later.)
Click the SIOU Tab when the PLC routing table is displayed, right-click the local PLC's icon, and select Set Gateway Counter
from the menu.
Check the routing tables for errors.
Select Options – Check Routing Table for errors from the PLC routing table's menu.
Save the created routing tables.
Select File – Save Local Routing Table File from the PLC routing table's menu.
Connect online with the PLC that is directly connected to the CX-Integrator (making it the target PLC).
Select Network – Auto Online or Network – Work Online from the CX-Integrator's menu bar.
Read the saved routing tables.
Select File – Open Local Routing Table File from the PLC routing table menu.
Transfer the routing tables to the PLC (from the computer to the target PLC).
Select Options – Transfer to PLC from the PLC routing table menu.
Create the FINS local routing tables (in the PLC routing tables).
Create the local network table.
Create the relay network table.
3-1-5 Operating Procedures Prior to Routing Table Transfer
3-1 Routing Table Overview