FQM1-TER01 Omron, FQM1-TER01 Datasheet - Page 80

no-image

FQM1-TER01

Manufacturer Part Number
FQM1-TER01
Description
5M 4COND 22AWG TPE ST MALE M12
Manufacturer
Omron
Datasheet

Specifications of FQM1-TER01

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
FQM1TER01
Power Supply Unit Specifications
General Specifications
Dimensions
Weight
Safety measures
Power Supply Unit
Supply voltage
Operating voltage
and frequency
ranges
Power consumption 100 VA max.
Inrush current
(See note 1.)
Output capacity
Output terminal
RUN output
Insulation resis-
tance
Dielectric strength
Noise immunity
Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
Shock resistance
Ambient operating
temperature
Ambient operating
humidity
Atmosphere
Ambient storage
temperature
Grounding
Item
Item
CJ1W-PA205R
100 to 240 V AC (wide-range), 50/60 Hz
85 to 264 V AC, 47 to 63 Hz
At 100 to 120 V AC:
15 A/8 ms max. for cold start at room temperature
At 200 to 240 V AC:
30 A/8 ms max. for cold start at room temperature
5.0 A, 5 VDC (including supply to Modules)
0.8 A, 24 VDC
Total 25 W max.
Not provided.
Contact configuration: SPST-NO
Switching capacity:
250 V AC, 2 A (resistive load)
120 V AC, 0.5 A (inductive load)
24 VDC, 2 A (resistive load)
24 VDC, 2 A (inductive load)
20 M min. (at 500 VDC) between AC external and GR terminals (See note 2.)
2,300 V AC 50/60 Hz for 1 min between AC external and GR terminals (See note 2.)
Leakage current: 10 mA max.
1,000 V AC 50/60 Hz for 1 min between DC external and GR terminals (See note 1.)
Leakage current: 10 mA max.
2 kV on power supply line (conforming to IEC61000-4-4)
minutes total (Time coefficient: 8 minutes
JIS C0040)
147 m/s
0 to 55 C
10% to 90% (with no condensation)
Must be free from corrosive gases.
Less than 100
20 to 75 C
Note
49
All models are each 5 kg max.
Conforms to EC directives and C-Tick. (UL certification pending.)
2
3 times each in X, Y, and Z directions (conforming to JIS C0041)
90
80 mm (W
(1) Disconnect the Power Supply Unit's LG terminal from the GR terminal
(2) Do not apply more than 600 V when testing the dielectric strength of an-
when testing insulation and dielectric strength. Testing the insulation and
dielectric strength with the LG and GR terminals connected will damage
internal circuits.
alog I/O terminals. Applying more than 600 V may damage the internal
elements.
H
D) (not including cables)
Specifications
coefficient factor 10 = total time 80 min.) (conforming to
Specifications
CJ1W-PA202
50 VA max.
At 100 to 120 V AC:
20 A/8 ms max. for cold start at room temperature
At 200 to 240 V AC:
40 A/8 ms max. for cold start at room temperature
2.8 A, 5 VDC (including supply to Modules)
0.4 A, 24 VDC
Total 14 W max.
Not provided.
2
in X, Y, and Z directions for 80
Section 2-2
53