Words in the Serial PLC Link Area that are not used for Serial PLC Links can be used only in the program as
work words. Bits in the Serial PLC Link Area can be force-set and force-reset.
The contents of the Serial PLC Link Area will be cleared in the following cases:
1. The operating mode is changed from PROGRAM to RUN or MONITOR mode or vice-versa.
2. The FQM1’s power supply is turned OFF and ON again.
3. The Serial PLC Link Area is cleared from the CX-Programmer
4. PLC operation is stopped when a fatal error other than an FALS(007) error occurs. (The contents of the Se-
B-8
The DeviceNet Area consists of 600 words from CIO 3200 to CIO 3799. Words in the DeviceNet Area are allo-
cated for DeviceNet remote I/O communications (with fixed allocation).
The FQM1 can be used in Slave mode only, so part of this area is used when memory is allocated by the fixed
allocation method. Words that aren't used by DeviceNet devices for DeviceNet remote I/O communications can
be used only in the program as work words.
Words in the DeviceNet Area are allocated to Slaves using fixed allocations according to fixed allocation setting
1, 2, or 3. The default setting is fixed allocation area 1.
Data is exchanged regularly to Slaves in the network (independent of the program) through the DeviceNet Unit.
Bits in the DeviceNet Area can be force-set and force-reset.
Note
I/O Memory
Fixed Allocation Area 1
Fixed Allocation Area 2
Fixed Allocation Area 3
rial PLC Link Area will be retained when FALS(007) is executed.)
CJ1M CPU
Unit
(1) The FQM1 supports the CJ1W-DRM21 Master Unit operating in Remote I/O Slave mode only. The
(2) The FQM1 does not support the CJ1W-DRM21 Master Unit’s message communications function.
(3) To allocate memory from a Programming Device (user-set allocation), either connect the CX-Inte-
(4) There are two ways to allocate I/O in DeviceNet networks: Fixed allocations according to node ad-
DeviceNet Area
Area
RS-232C
port
Master Unit cannot be used in Master mode.
Use the Master Unit only as a Remote I/O Slave.
grator to the host PLC (such as a CJ1M) in which the Master Unit is mounted or use a Configurator
to make the settings. With the FQM1-CM002, the FQM1’s allocated DM Area can also be used.
dresses and user-set allocations. For details on word allocations, refer to the DeviceNet Operation
Manual (W267).
• With fixed allocations, words are automatically allocated to the slave in the specified fixed alloca-
tion area according to the node addresses.
Serial PLC Link
Coordinator
Module 1
RS-232C
port
CIO 3370
CIO 3570
CIO 3770
(Master to Slaves)
Output Area
Coordinator
Module 2
RS-232C
port
Serial PLC
Link Area
CIO 3270
CIO 3470
CIO 3670
(Slaves to Master)
Input Area
Appendix B
375