NT30-KBA04 Omron, NT30-KBA04 Datasheet - Page 207

no-image

NT30-KBA04

Manufacturer Part Number
NT30-KBA04
Description
ANTI GLARE COVER FOR NT31
Manufacturer
Omron
Datasheets

Specifications of NT30-KBA04

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
198
Inputting Numeric Values
Reference: When the Storage Type is BCD, the numeral memory table’s signed binary data
Reference: Since values input at the PT are handled as signed binary data, be sure to ob-
Note When the numeral values entered are confirmed, upper/lower limits are
is converted to data for storage in the host word (BCD data) and written to the
host. If the value is negative the most significant digit in the word is set as F. This
means that the maximum number of digits for a negative number (integer part +
decimal fraction part) is seven.
serve the following upper/lower limit settings at the Support Tool when numbers
are being input in hexadecimal with its unlimited input range.
When the Storage Type is Binary, the contents of the numeral memory table are
written without alteration to the host word.
However, when a negative number is written to a numeral memory table whose
number of allocated words at the host is one, it is stored immediately after input
as a 16-bit negative number.
The data is stored in the numeral memory table as a 32-bit negative number in
this case as well.
Upper/Lower (Max./Min.) Limit Check
The PT has a function to check the correctness of an input numeric value to pre-
vent a numeric value outside the allowable range from being input so that the
input of an illegal value will not adversely affect the system.
The upper/lower (max./min.) limit check is executed in the timing indicated be-
low according to the type of a numeral setting input field.
For a thumbwheel type numeral setting input field, the check is executed each
time the increment/decrement key of each digit position is pressed.
With a thumbwheel type numeral setting input field, if n...n < m...m [upper limit:
1n...n, lower limit: 0m...m (n and m are arbitrary values at each digit)], carry over
and underflow are not possible at the highest digit position.
Example:
If the upper limit value and the lower limit value are 1200 and 201, respectively,
the numeric value can be changed only in the following range: from 201 to 999 if
an initial value is a 3-digit value and from 1000 to 1200 if an initial value is a 4-digit
value.
The reason for this is that the upper/lower (max./min.) limit check function does
not allow the numeric value at the highest digit position to change from 0 to 1 or
from 1 to 0.
To avoid this, set the upper and lower limit values so that n...n y m...m, or pro-
vide a touch switch separately to write a numeric value for carry over or under-
flow.
checked.
• The following values are recognized internally in the PT.
• In the Support Tool, the upper/lower limits are set in decimal. (The $ prefix can
Using the figures above, the following table shows the upper/lower limits to be
set at the Support Tool.
1 word:
2 words: 8000 0000
be added to input hexadecimal values.
value in the numeral memory table changes.
8000
(–2,147,483,648 ↔ 0 ↔ 2,147,483,647 decimal)
H
↔ 0000
H
↔ 0000 0000
H
↔ 7FFF
H
H
(–32,768 ↔ 0 ↔ 32,767 decimal)
↔ 7FFF FFFF
H
Section
2-12

Related parts for NT30-KBA04