6-2-2 Errors Occurring during Operation and Their Remedies
Operational Errors (Other than Device Monitor Errors)
Device Monitor Function Errors
416
Responding to Displayed Error Messages
[Address Setting Error]
Addressing Error exists in the
Screen.
Correct address setting by the
Support Tool.
[Memory Table No. Error]
Memory table No. is out of limit.
Correct the table No. by the
Support Tool.
[Programming Console Error]
Setting of Programming Console
Function is inadequate. It can be
caused by:
• This PLC does not support Pro-
• This PLC does not su
• Protocol mismatch. Set the PLC
• “PROGRAMMING CONSOLE”
• “PROGRAMMING CONSOLE”
[Programming Consol Error]
Programming Console Function
does not RUN. It can be caused
does not RUN. It can be caused
by:
• Connecting cable is faulty.
• “PROGRAMMING CONSOLE”
• PROGRAMMING CONSOLE
• Protocol mismatch between the
The setting is wrong.
Can’t write while running.
The memory can’t be written.
gramming Console Function.
to NT Link.
is connected to PLC.
is connected to PLC.
PT and PLC. Set the PLC to NT
Link.
Link.
Message
Error
ort Pro-
A word address that doesn’t
exist in the PC was specified
in the popup input window.
An attempt was made to
change word contents while
the PC was in RUN mode.
An attempt was made to write
to a read-only or
write-protected area.
The table below shows the errors that can occur during operation of the PT and
their remedies.
The host side allocated words
and bits set with the Support Tool
are incorrect.
The memory table number set
with the Support Tool is outside
the range for the number of
memory tables set in the system
memory.
The communication settings are
incorrect.
The PC used does not support
the Programming Console
function.
A programming Console is
connected.
The connecting cable is
defective.
Malfunction due to external noise
A Programming Console is
connected.
The communication conditions at
the PC have been changed in
accordance with the PT
Programming Console function.
Probable cause
Cause
Input a word address that exists in the PC
Switch the PC to MONITOR or PROGRAM mode. The
PC’s operating mode can be changed from any one of
the Device Monitor screens.
Write to a read/write area in the connected PC. If the
area is write-protected, clear the write-protection and
try writing the data again.
Set correct words and bits after checking the
area used at the host side by referring to
Appendix D PC Memory Maps (page 429), and
the manual for the PC being used.
Either increase the number of memory tables in
the System settings under PT Configuration at
the Support Tool, or set the memory table
number again within the established range.
Set the communication method/communication
port as follows when using the Programming
Console function.
- With C series PLC : NT Link : 1 : 1
- With CS1 series PLC : NT Link : 1 : N
Not all PCs support the Programming Console
function. Check the model of the PC you are
using. ( 2-16-9 Programming Console Function ,
page 248)
It is not possible to use a Programming Console
and the Programming Console function at the
same time. Disconnect the Programming
Console.
Check the cable connection and perform a
conductivity test. If there is a fault, replace the
cable.
Carry out grounding work in accordance with the
conditions. (Refer to Grounding in section 3 in
the Setup Manual .)
It is not possible to use a Programming Console
and the Programming Console function at the
same time. Disconnect the Programming
Console.
Set the communication conditions at the PC to
match the conditions set in the System Menu.
Remedy
Remedy
Section
6-2