CRT1-OD16SL-1 Omron, CRT1-OD16SL-1 Datasheet - Page 611

no-image

CRT1-OD16SL-1

Manufacturer Part Number
CRT1-OD16SL-1
Description
16 Out PNP Cage Clamp
Manufacturer
Omron
Datasheet

Specifications of CRT1-OD16SL-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Troubleshooting
Analog I/O Slave
Units (Inputs)
Analog I/O Slave
Units (Outputs)
Temperature Input
Units
Model
The disconnection display
does not clear.
No disconnection display.
The conversion cycle is too
long.
The expected value is not held
when communications errors
occur.
The 1/100 Display Mode has
been set, but the display reads
0.
The temperature range
counter is not counting even
though the temperature value
is set as the count condition.
The Top/Valley Count Over
Flag will not go ON.
The comparator does not oper-
ate as expected even though
the function and hysteresis
value have been set.
Problem
• The Sensor is disconnected.
• Disconnection is not dis-
• The setting of the number of
• The processing time gets
• The output value that is set
The allocated word is the one
word in the normal display
area.
The comparator function is not
effective.
• The top/valley hold function is
• The hysteresis setting is too
• The hysteresis setting is 0.
• The temperature display set-
• The decimal point position
played for ranges other than 1
to 5 V and 4 to 20 mA.
AD conversion points is on
the maximum (4 points).
longer each time a function is
added.
for communications errors is
incorrect.
not enabled.
high.
ting has been switched (°C to
°F or vice versa).
was read incorrectly.
Cause
• Restore the Sensor connec-
• Check the connected Sensor
---
• Reduce the number of points
• Delete any unused functions,
• Check the output setting for
Either change the default con-
nection path to the 1/100 dis-
play area or select a
connection path in the Master
Unit for the 1/100 display area.
Enable the comparator. (The
power must be turned OFF
and then ON again.)
• Enable the top/valley hold
• Adjust the hysteresis setting.
Check the decimal point posi-
tion and °C/°F display for the
input type and display mode.
If these settings have been
changed during operation,
check the comparator and hys-
teresis settings and correct if
necessary.
tion.
and input type again.
if some inputs are unneces-
sary, and execute conversion
again.
and execute conversion
again.
communications errors.
function. (The power must be
turned OFF and then ON
again.)
Possible correction
Section 12-2
587