Summary of the Analog Output Slave Units
1,2,3...
■ Output Range: 0 to 20 mA
Data of 0000 to 1770 Hex (0 to 6000) is converted to current from 0 to 20 mA
and output. The output data range for which conversion is possible is from
0000 to 189C Hex (0 to 6300) and for this case the output data becomes from
0 to 21 mA.
Setting of output range is performed using Analog Output Slave Unit DIP
switches, CX-Integrator, or Explicit message.
The method for setting the output range using CX-Integrator is described
below.
Please see "11-1 CX-Integrator" on page 481 regarding details for CX-Inte-
grator.
1. Turn ON the power to the CompoNet Slave Unit.
2. Double-click the icon of the Analog Output Unit to set in the Network Con-
3. Select the tab for the channel for which you would like to change the range
4. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
5. Click the OK Button and exit the window.
FFFF
figuration Window to open the Configuration Window. (Alternatively, right-
click the icon and select Parameters - Edit from the pop-up menu.)
and select any output range from the pull-down list of "Output Range".
download the data, and then click the Reset Button to reset the Unit.
21 mA
20 mA
0 mA
Current
0000 (0)
(6000)
1770
(6300)
189C
7FFF
Conversion data
Hexadecimal (decimal)
Section 6-3
321