Functions Common to All Slave Units
11-2 Functions Common to All Slave Units
11-2-1 Automatic Baud Rate Detection
Description
11-2-2 Hold/Clear Outputs
Description
Procedure Using CX-
Integrator
486
1,2,3...
This section describes the functions common to all CompoNet Slave Units
and the procedures for using these functions.
The functions described in 11-2-1 Automatic Baud Rate Detection and 11-2-2
Hold/Clear Outputs are supported by Bit Slave Units with Compact Connec-
tors.
The CompoNet Slave Units are automatically set to the same baud rate as the
Master Unit. It is not necessary to set the baud rate separately for any Slave
Unit.
The baud rate is set when communications is established with the Master Unit
after the power is turned ON. The baud rate setting is stored in memory until
the power is turned ON again or until the Master Unit baud rate setting is
changed.
Output Units can be set to hold or clear outputs when an error occurs.
1. Turn ON the power to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
3. Click the OUT Tab.
4. Double-click I/O Comment for the terminal to be set. The Edit Terminal
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
Window will be displayed. Select either to clear or hold outputs when a
communications error (Fault Action) and idle state (Idle Action) occurs, and
then click the OK Button.
Section 11-2