Functions of Digital I/O Slave Units
11-3-4 Contact Operation Monitor
Description
498
Note
4. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
5. Click the OK Button and exit the window.
The number of times each input contact or output contact is turned ON can be
counted (resolution: 50 Hz max.) and stored in Slave Unit memory. (This data
can be read using the CX-Integrator or using explicit messages.)
A monitor value can be stored in the Slave Unit memory so once the number
of contact operations reaches the monitor value, a flag in a status area in the
Slave Unit turns ON to notify the Master Unit. The notification details can be
read using the CX-Integrator or using explicit messages.
(1) The contact operation monitor and the total ON time monitor cannot be
(2) This function does not operate if the I/O power is not turned ON.
OFF → ON
• No. of times measured: 0 to 4,294,967,295
• Measurement unit: No. of operations
download the data, and then click the Reset Button to reset the Unit.
used for the same contact at the same time. Select only one of these
functions under the Detection Mode.
No. of
operations
Slave Unit
Output device
(e.g., relay)
I/O power supply
(Stored data: 0000 0000 to FFFF FFFF hex)
Stored in Slave Unit memory
No. of times output
contact turns ON:
1
Section 11-3
2
3