Connecting Cables and Terminating Resistor
3-4-4
Round Cable I
82
Connection Locations for Terminating Resistor
Note
A Terminating Resistor must always be connected to the trunk line and each
sub-trunk line on the opposite end from the Master Unit or Repeater Unit.
Connect the cable wires to a DRS1-T Terminating Resistor.
(1) Do not connect the Terminating Resistor at the same end of the cable as
(2) When the cable is branched at the locations shown in the figure below,
Round cable I
Master Unit
the Master Unit or Repeater Unit.
connect the Terminating Resistor at the end of the line so that the length
of a is greater than b.
Master Unit
Terminating Resistor
Terminating
Resistor
Sub-trunk line
Sub-trunk line
Repeater
Unit
Trunk line
Repeater
Unit
Slave Unit
Slave Unit
Trunk line
Slave Unit
b
Connect the Terminating
Resistor on the opposite
end of the sub-trunk line
from the Repeater Unit.
Cable length: a > b
Connect the Terminating
Resistor on the opposite
end of the trunk line from
the Master Unit.
a
Terminating Resistor
Slave Unit
Slave Unit
Terminating Resistor
Section 3-4