Setting Using the CX-Integrator
Adjusting the Low
Limit
Analog I/O Slave Unit (output) Functions
1,2,3...
1. Turn ON the power supply to the CompoNet Slave Unit.
2. Double-click the icon of the Slave Unit to set in the Network Configuration
3. Select the Tab Page for the output to be adjusted, and click the Adjust-
4. Output the value from the Master Unit that is equivalent to 0%. Always per-
5. Adjust the analog value that is output from the terminal using the Lower
0 to 20 mA
–10 to 10 V
4 to 20 mA
Output range
Window to open the Configuration Window. (Alternatively, right-click the
icon and select Parameters - Edit from the pop-up menu.)
ment Button. (At this time, set the output range.)
form adjustment with the 0% value.
Adjustment slide bar, as shown in the following window. Repeat adjust-
ments until the correct 0% value is output from the output device. After
compensation is completed, click the Fix Lower Adjusting Value Button.
–11 to –9.0 V
3.2 to 4.8 mA
0.2 to 1.0 mA
Low Limit
19 to 21 mA
9.0 to 11 V
19.2 to 20.8 mA
High Limit
Section 11-5
535