Indicator Meanings and Troubleshooting
12-1 Indicator Meanings and Troubleshooting
580
MS
NS
MS
NS
MS
NS
MS
NS
NS
NS
MS
NS
MS
NS
NS
NS
MS and NS
indicators
Lit green
Lit green
Lit green
Not lit
Lit green
Flashing
green
Lit red
Not lit
Flashing
red
Not lit
Lit green
Lit red
Lit green
Flashing
red
Flashing
red
Lit red
Remote I/O communi-
cations or message
communications are in
progress.
Synchronizing speed.
Waiting for a connec-
tion.
Watchdog timer error
Illegal switch setting
EEPROM checksum
error
Configuration error
Communications time-
out
Configuration error
Meaning
Remote I/O communi-
cations are being exe-
cuted.
Waiting for connection
with Master Unit.
Waiting for a connection
with the Master Unit to
be established.
A watchdog timer error
has occurred in the
Slave Unit.
A DIP switch or other
switch setting is illegal.
EEPROM data error
• The same node
• Repeater Unit configu-
---
A node address has
been set out of range.
address has been
used more than once.
ration error
Either remote I/O communications, message
communications, or both are being executed.
Status is normal.
If only certain Slave Units show this status,
check that the baud rate is the same and then
restart the Slave Units.
Replace the Slave Unit. Alternatively, check the
Expansion Unit connection.
Check the switch settings then restart the
Slave Units.
Use the CX-Integrator to restore the default
data.
Check that the node address is set within the
allowable range and that it is used only once.
Check the Repeater Unit configuration and
then restart the Slave Units. If the node
address and Repeater Unit configuration are
correct, check the following items, and then
restart the Slave Units.
• Are the baud rates the same for the Master
• Is the cable length (trunk line/branch lines)
• Is the cable disconnected or loose?
• Is there a Terminating Resistor on each end
• Is there too much noise?
Check the following items then restart the
Slave Units:
Is the baud rate the same for the Master Unit
and Slave Units?
Is the cable length (trunk line/branch lines)
OK?
Is the cable disconnected or loose?
Is there a Terminating Resistor on each end of
the trunk line?
Is there too much noise?
Make sure that the node address is set within
the specified range, and then restart the Slave
Unit.
Unit and Slave Units?
OK?
of the trunk line?
Remarks
Section 12-1