CRT1-ID16TAH Omron, CRT1-ID16TAH Datasheet - Page 595

no-image

CRT1-ID16TAH

Manufacturer Part Number
CRT1-ID16TAH
Description
16 In NPN 3 Tier
Manufacturer
Omron
Datasheet

Specifications of CRT1-ID16TAH

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Temperature Input Unit Functions
Note
1. The bias compensation value may not be accepted if there is a large tem-
2. Always test the indication accuracy after making user adjustments to verify
STV
perature difference between the Terminal Block and ZERO-CON (0°C
bath). If this problem occurs, correct the adjustment system by using a
ZERO-CON compatible with the sensor being adjusted or other means.
that the adjustments are correct. Test the indication accuracy at three
points: the lower limit value, an intermediate value, and the upper limit val-
ue.
Note Always use the compensating conductors (the same kind that will be
• Connect the external devices as shown in the following diagram.
• After verifying that the ZERO-CON is set to 0°C, set the STV’s output
voltage to produce a voltage equivalent to the test voltage.
used with the sensor being adjusted) to connect the ZERO-CON to
the CRT2-TS04T’s input terminals.
OUTPUT
ZERO-CON
(0°C bath)
INPUT
Compensating
conductors
CRT1-TS04T
Input (+)
Input (–)
Section 11-6
571