10-1 Status Areas
Warning Status Area
472
An Repeater Unit has two status areas: the Warning Status Area and the
Alarm Status Area. The status flags in these areas are turned ON and OFF
based on the threshold/monitor values set for each function in that Unit. When
any of the bits in the status area of the slaves connected to the Master Unit
turns ON, the corresponding bit (bit 12 is for warning status area notices and
bit 13 is for alarm area notices) of the status flag in the Master Unit turns ON.
The Repeater Unit's status area information can be read by using the CX-Inte-
grator or explicit messages.
The Repeater Unit’s Warning Status Area contains the following 16 bits.
These bits indicate minor errors in the Unit.
Bit
10
11
12
13
14
15
Master Unit
0
1
2
3
4
5
6
7
8
9
Reserved
Reserved
Network Power Voltage Drop Flag
OFF: Normal
ON: Error (Voltage dropped below
threshold.)
Unit Maintenance Flag
OFF: Normal
ON: Error (Threshold exceeded.)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Downstream Network Voltage Flag
OFF: Normal
ON: Error (Power OFF.)
Reserved
Reserved
Reserved
Reserved
Reserved
Transmitted
to Master Unit
The status bit detection allocated to the master is OR of all
slaves
Content
The Repeater Unit has two status areas:
the Warning Status Area and the Alarm Status Area.
Repeater Unit
---
---
Turns ON when the voltages drops
below the voltage set for the network
power voltage monitor function.
Turns ON when the threshold set for
the Unit Conduction Time Monitor
function is exceeded.
---
---
---
---
---
---
Turns ON when the power supply to
the downstream network is OFF.
---
---
---
---
---
Description
Section 10-1