3-6-4
Connecting External I/O for Slave Units
Connecting to Screw-less Clamp Terminal Blocks
Note
■ Applicable Pin Terminals
■ Wiring to the Screw-less Clamp Terminal Block
When using a DCN4-MD4 Multidrop Connector to branch a Communications
Cable, bind together the loose wires where the cable comes out of the Hood
Cover. Wire the Communications Cable and loose-wire cable so that they do
not interfere with each other.
For Slave Units with screw-less clamp terminal blocks, the terminal blocks can
be easily wired by inserting pin terminals. Follow the procedure below to con-
nect the external device cable to a screw-less clamp terminal block.
When wiring an external device cable to a screw-less clamp terminal block,
special pin terminals must be placed on the cable wires. The applicable pin
terminals are listed in the following table.
The pin terminal conductor should be about 8 to 10 mm in length.
Inserting Pin Terminals
Insert the pin terminal all the way to the back of the terminal hole.
Removing Pin Terminals
Press down the release button next to the terminal hole with a small flat-blade
screwdriver and pull out the pin terminal while the release button is down.
The following screwdriver is recommended for removing pin terminals.
H0.5/14 orange
H0.75/14 white
H1.5/14 red
SD0.6 × 3.5 × 100 Flat-blade
Screwdriver
Insert the pin terminal all the way to the back.
Name
Release button
Small flat-blade screwdriver
Conductor length: 8 to 10 mm
Model
Applicable wire size
0.5 mm
0.75 mm
1.5 mm
2
2
/AWG20
/AWG16
2
/AWG18
Weidmuller Co. Ltd.
Manufacturer
PZ6 roto
Crimp tool
Weidmuller Co. Ltd.