CV500BSC51 Omron, CV500BSC51 Datasheet - Page 80

no-image

CV500BSC51

Manufacturer Part Number
CV500BSC51
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BSC51

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Using the Status Byte for Error Processing
Parameter
error
(Bit 7 of n+7
ON)
GP-IB error
(Bit 8 of n+7
ON)
Error Flag
The interface message number specified in buffer
memory is invalid.
The “number of peer devices” or “peer device
addresses” specified in buffer memory are invalid.
The “number of receiving device addresses” or
“receiving device addresses” specified in buffer
memory are invalid.
The “peer device addresses” were not set when
making a serial polling request.
An IORD(222) or IOWR(223) instruction addressed
an address beyond the range of buffer memory.
A non-existent device address was specified in
buffer memory for the “transmitting device address”
or “receiving device address.”
The communications cable is not connected prop-
erly.
The communications peer device cannot be found. Check whether there are two or more devices with
A transmission error occurred because of noise in
the system.
Probable cause
shows the errors indicated in the status area as well as the steps most likely
to correct the errors.
Error Flags in n+7 (n = CIO 2000 + (10
D15
D14
D13
D12
D11
D10
D9
D8
D7
Parameter error
GP-IB error
Timeout Error
Command Error
D6
Set this parameter correctly.
Set these parameters correctly.
Set these parameters correctly.
Set the peer device addresses when making a
serial polling request.
Check the “starting address” and “number of words
to transfer” settings so that the instruction does not
exceed the range of the buffer memory.
Set the addresses correctly.
Check the connecting cable to the other device.
Check whether the connectors are damaged or
attached incorrectly.
the same device address setting in the system.
Check whether there are two or more Controllers in
the system.
Check the other device’s power supply.
Verify that the other device’s power supply is ON
before the Controller starts communicating.
Change cable routes or reduce noise in the envi-
ronment.
D5
D4
D3
unit number))
D2
Possible remedy
D1
D0
Section 7-2
63