Service Request and
Serial Poll
1-4
1-4-1
Comparison with other OMRON Units’ GP-IB Functions
Compatible PLCs
Master/Slave modes
Control from the program
Parallel poll responses
Execution of Enhanced
BASIC commands
SRQ transmissions
Comparison with other OMRON Units’ GP-IB Functions
Model
Functional Comparison
1,2,3...
Note The GP-IB Interface Unit automatically controls the ATN line status to switch
CS-series
Master and Slave modes
Operation can be controlled by writing data to the Unit’s buffer
memory from the ladder program with the IOWR/IORD
instructions (CS-series and C1000H/C2000H PLCs) or WRIT/
READ instructions (CVM1 and CV-series PLCs.)
Not supported.
Supported.
Supported.
1. The Controller sets the ATN line to “L” and sends the UNL command. This
2. The Controller sends the TA (Talker address) and LA (Listener address).
3. The Controller sets the ATN line to “H” to put the bus in data mode. At this
the bus between command mode and data mode and automatically sends
commands such as UNL, TA, and LA.
A device connected to the GP-IB system can generate an interrupt to the sys-
tem Controller for a service request by setting the SRQ line to “L.”
When the Controller detects the “L” level in the SRQ line, it performs a Serial
Poll operation to identify the device that generated the interrupt. The Control-
ler performs the Serial Poll operation by requesting the transfer of each
device’s status byte in order, as shown in the following diagram.
DIO1 to DIO8
CS1W-GPI01
command inactivates the connected GP-IB devices.
Two or more Listener addresses can be specified. This step determines
the new Talker and Listener(s) and the relevant GP-IB devices will standby.
point, data will be transferred between the Talker and Listener(s).
ATN
SPE: Serial-poll enable
TA: Talker address
STB: Status byte
SPD: Serial-poll disable
UNL
CVM1, CV-series, and
C1000H/C2000H
Slave mode only
SPE
C500-GPI01
TA
STB
TA
CVM1 and CV-series
Master and Slave modes
Control operation with the
BASIC program in the
BASIC Unit.
Supported.
Not supported.
STB
CV500-BSC51/61
...
Section 1-4
SPD
9