Master Mode Program Examples
6-1-4
Program Example
48
Set Local Status
This program sets a device to local status.
The control line REN is set to high if there is no address specification. A GTL
message is sent if there is an address specification.
In this example, an address is specified and a GTL message is sent. The GTL
message is sent when W000.00 is turned ON.
First Cycle Flag
First Cycle Flag
W100.01
W100.00
2000.00
2007.07
W000.00 W100.00
W100.01
A200.11
A200.11
2005.00
2005.00
Equal Flag
(CF006)
IOWR(223)
W100.01
W100.00
END(001)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
MOV(21)
W200.00
D00010
D17000
2000.00
2000.00
D00010
D00011
D00012
D17000
D17001
#0004
#0001
#0002
#0000
#0003
#0000
RSET
SET
SET
Turns ON the Send Interface Message
Request Bit.
Turns OFF the Send Interface Message
Bit if the message was sent properly and
the Interface Message Send Completed
Flag was turned ON.
Turns ON W200.00 if an error occurred
and the Parameter Error Flag was
turned ON.
Stores the data that will be written in
buffer memory.
Interface message number: 0004 Hex
Number of peer devices: 0001 Hex
Peer device address: 0002 Hex
Sets the parameters for IOWR(223).
Unit number of destination device:
0000 Hex
Number of words to transfer: 0003 Hex
IOWR(223) writes the interface message
number and other parameters to buffer
memory beginning at buffer memory
address 0000 Hex.
Section 6-1